TAC32H Virtual Controller v0.2

ThyssenKrupp TAC32H hydraulic, IOD / CPUA / CWIL + tape selector. Readings are tagged printed (print 2204 or manual), derived (worked out from the logic) or unconfirmed.

Car and hoistway

Car calls (COP) - hall buttons are at the landings
Mode:
Fire service
Car lightFan
Phase I key
Smoke
Phase II key

Stop switches

Operated (open) switches break the safety string or the car-stop branch. Use them to check the string with the meter.

Job configuration

Adjustments

Z44 run stall time (default 20 = 2.0 s), P17 up slowdown and P18 down slowdown (counts of 1/40 in; 939 and 683 are the manual's 100 fpm values). Halve P17 to run the terminal slowdown test: the car reaches the terminal slowdown magnet too fast and logs 1062 and 981.

UIT (user interface tool)

Separate reset button on the CPUA card, not part of the UIT keypad.

Digital meter

-----
Select a red and black lead point.
RedBlack

Jumpers and fuses

FromTo
Fuses (pull / replace)
No jumpers installed.

Jumpers are temporary. Bypassing a safety device is for troubleshooting only and must be removed before the car is returned to service. Fuse buttons pull a fuse (blown) or replace it.

Test points

Controller fault log

Inject a fault (instructor)

← All simulators